Avoid VFD Downtime: A Deep Dive into Ground Faults


Variable Frequency Drives (VFDs) play a critical role in modern industrial applications by controlling motor speed and optimizing energy use. However, like any electrical system, VFDs are not immune to issues. 

One of the most common problems encountered is a ground fault, also known as an earth fault. Ignoring this issue can lead to significant downtime, equipment damage, and safety hazards. So, how do you identify and address ground faults in your VFD system effectively?

Let’s dive into what ground faults are, how they occur, and practical solutions to keep your operations running smoothly.

What is a Ground Fault?

In simple terms, a ground fault occurs when electricity escapes the intended circuit and flows to the ground. 

This can happen at any point in the motor circuit and is typically indicated on the drive’s HMI with an error message such as “GF” or “EF2.” Ground faults compromise the efficiency and reliability of VFD systems, making their identification and resolution crucial.

Common Causes & Ground Fault Troubleshooting Steps

Ground faults can stem from several areas within the VFD system. Below are the primary causes and actionable solutions for troubleshooting this issue:

1. Motor Issues

The motor can sometimes short due to various internal and external factors like voltage spikes, overheated windings, aged insulation, or an external conductive containment breach that is connecting the motor windings to ground.

Solution:

  • If motor windings are compromised: the motor must be rewound or replaced. ESR Motor Systems can assist with these services. Please call our team at 1-803-233-4040 for further assistance.
  • To confirm the motor is the issue, disconnect the drive’s output leads while the power is off. Then power up the drive and issue a run command. If the fault disappears, the motor or the leads are the problem.
  • If the fault persists while disconnected, the VFD itself may have an issue. It may be time for a replacement, connect with our team and we’ll help you find exactly what you need.

2. Cabling Issues

Cabling problems are another common source of ground faults. If the insulation on the cables was compromised, current can bleed to the ground if it touches a conductor. Insulation can become comprised due to several factors:

Melting After an Overcurrent Event
Damage During Installation: For example, pulling cable that isn’t highly flexible causing it to bend and break.
External Sources: Such as critters thinking it’s a snack.

Solution:

• Use a megohmmeter to test the insulation of the cables. If the leads fail the test, they are likely the cause of the ground fault.
• Replace or repair damaged cables and ensure proper installation practices to prevent recurrence.


Contact ESR Motor Systems for Your VFD Needs